March 2026

Conference Paper

Assessing the Impact of Variable Air Volume Box Damper Stuck Faults Using a Building Automation System and Building Energy Simulation Model

By:
Jung, Sungkyun ; Yoon, Yeobeom ; Im, Piljae
Page Number:
790-799
Book Title:
Proceedings of SimBuild Conference 2024
Publication Date:
March 12, 2026
Publisher Location:
International Building Performance Simulation Association, United States of America
Conference Name:
IBPSA-USA SimBuild 2024
Conference Location:
Denver, Colorado, United States of America
Conference Sponsor:
IBPSA-USA (International Building Performance Simulation Association)

Abstract

The study examines the impact of variable air volume (VAV) damper stuck faults on the system operation, building indoor conditions, and reheating energy consumption. This study includes both experimental and simulation studies for five test scenarios, including a fault-free scenario. We implemented VAV damper stuck fault through the building automation system (BAS). Results show that a damper stuck in a high opening position (60% damper opening) results in supplying an excessive amount of cold air from the rooftop unit (RTU) to the conditioned zone, increasing reheating energy consumption. The results of this research can serve as a foundational resource for developing fault detection algorithms.