- By:
- Ademola, Adedasola A.; Roland, Brandis; Schuetzinger, Andreas; Simons, Bart; Dorpmanns, Luc; Pinceti, Andrea; Vance, Katelynn; Korede, Ibukunoluwa; Orndorff, Robert; Hannah, Kyle; J. TILL, MICAH; Lamb, Mike; Gardner, R. Matthew; Liu, Yilu
- Journal Name:
- IEEE Transactions on Power Delivery
- Page Number:
- 447-458
- Volume:
- 40
- Issue Number:
- 1
- Publication Date:
- April 16, 2026
- View DOI Listing:
- https://doi.org/10.1109/TPWRD.2024.3502642
Abstract
Geomagnetic-induced current (GIC) flow in power grids can cause undesirable effects such as transformer overheating, harmonics, higher reactive power demand, etc. Many simulation models have been developed to study these effects, but real-world verification on modern transformer designs is rare. This paper presents the first long-duration GIC field test in the U.S. performed on high-voltage, grid-connected transformers featuring winding clamps and tie rods instead of conventional tie bars. Field measurements were taken to evaluate GIC effects. These measurements also aided in developing and validating thermal and electromagnetic transient (EMT) models of the transformers. During the test, significant current and voltage distortions were observed along with considerable transformer reactive power losses. Analysis of the field measurements showed that the transformers’ hottest spot was at the inner windings, and their k-factors were close to factory test and software default values. Thermal simulations indicated that the transformers would not violate their thermal limits even for a GIC waveform that peaks at about 200 A/phase. EMT simulations revealed that increased transformer loading may reduce GIC-induced reactive power demand and harmonics in certain scenarios. The study also highlighted potential inaccuracies in using the k-factor method to calculate transformer reactive power losses.